800 Vac Class gR NH fuses
Product description Eaton's BussmannTM series 800 Vac NH size fuses are specifically designed to meet the needs of branch circuit and transformer protection in photovoltaic (PV) inverter systems. The fuses are capable of interrupting low overcurrents associated with faulted PV systems (such as reverse current or multi-array faults).
Catalogue symbol
• Bladed with lugs 170M7350 to 170M7402
• Bolt holes no lugs 170M7353-B to 170M7402-B
Fuse size • NH1, 2 and 3
Technical data
• Volts: 800V a.c.
• Amps: 32 to 400 A
• Breaking capacity: 65 kA
• Class of operation: gR
Standards/Agency information
• UL 248-13 (file number E125085)
• IEC 60269-4 (see details in technical data table 1)
bladed version)
• 170H0236
• 170H0238
Compatible fuse holders (ordered separately ,only for use with bladed version)
• SD1-D
• SD2-D
• SD3-D
Catalog Numbers
|
Size |
Amps |
Vac |
Catalog Numbers |
|
NH1 |
32 |
800 |
170M7350 |
|
40 |
170M7351 |
||
|
50 |
170M7352 |
||
|
63 |
170M7353 |
||
|
80 |
170M7354 |
||
|
100 |
170M7355 |
||
|
125 |
170M7356 |
||
|
160 |
170M7357 |
||
|
200 |
170M7358 |
||
|
NH2 |
160 |
170M7397 |
|
|
200 |
170M7398 |
||
|
250 |
170M7399 |
||
|
NH3 |
315 |
170M7400 |
|
|
355 |
170M7401 |
||
|
400 |
170M7402 |
Carton Quantity
|
Amp Rating |
Carton Qty. |
|
32-400 |
10 |
Features
• NH size 1, 2 and 3 are compact to save enclosure space for greater design flexibility.
• Industry-leading low power loss provides greater efficiency and lower operating temperature.
• Dual indication feature and optional microswitches make system monitoring easier.
• Bolt-on version features common hole centers for standardizing busbar designs across the 63-400 amp range.
• Bolt-on version eliminates the need for a fuse block, reducing installation time and components.
• Compatible with Bussmann series PV NH base range
Standard features
• Compact design
• Low power loss
• Variation of fixing options
• Dual indicator feature
• Optional microswitches
Series: NH 800V Series, Class gR Fuse
Current: 32-400A
Voltage: 800Vac
Segment capacity: 63KA
Certification:- UL 248-13 (file number E125085)
-IEC 60269-4 (see details in data sheet)