          Best Solution For Your Business.  


Low-Peak™ LP-CC Class CC 600 Vac/300 Vdc, 1/2-30 A time-delay fuses

 

Catalog symbol:   LP-CC-(amp)

Description:

Bussmann™ series Ultimate protection Low-Peak Class CC current-limiting, time-delay fuses. Timedelay – 12 seconds (minimum) at 200% of rated current.

 

Specifications:

Ratings

Volts:   

  • 600 Vac

  • 300 Vdc (1/2 to 2-8/10 A, 20-30 A)

  • 150 Vdc (3-15 A)

Amps :  1/2-30 A

IR :

  • 200 kA Vac RMS Sym.

  • 20 kA Vdc

 

Agency information

  • UL® Listed Class CC, Std. 248-4, Guide JDDZ, File E4273

  • CSA® Certified; Class 1422-02, File 53787

  • CE

  • RoHS compliant

 

Catalog Numbers (Amps)

Catalog Numbers

Catalog Numbers

Catalog Numbers

  LP-CC-1⁄2

  LP-CC-2-1⁄2

  LP-CC-7-1⁄2

  LP-CC-6⁄10

  LP-CC-2-8⁄10

  LP-CC-8

  LP-CC-8⁄10

  LP-CC-3

  LP-CC-9

  LP-CC-1

  LP-CC-3-8⁄10

  LP-CC-10

  LP-CC-1-1⁄8

  LP-CC-3-1⁄2

  LP-CC-12

  LP-CC-1-1⁄4

  LP-CC-4

  LP-CC-15

  LP-CC-1-4⁄10

  LP-CC-4-1⁄2

  LP-CC-20

  LP-CC-1-1⁄2

  LP-CC-5

  LP-CC-25

  LP-CC-1-6⁄10

  LP-CC-5-6⁄10

  LP-CC-30

  LP-CC-1-8⁄10

  LP-CC-6


  LP-CC-2

  LP-CC-6-1⁄4


  LP-CC-2-1⁄4

  LP-CC-7



Carton quantity

Amp rating

Carton qty

1/2-30

10

 

Features:

  • 200 kA interrupting rating complies with NEC® Section 110.9 for today’s large capacity systems.

  • Fast short-circuit protection and dual-element, time-delay performance provide ultimate protection.

  • Reduces existing fuse inventory by up to 33% when upgrading to Low-Peak fuses.

  • Consistent 2:1 amp rating ratios for all Low-Peak fuses make selective coordination easy.

  • Time-delay characteristic avoids unwanted fuse openings from surge currents while fast response speed under fault conditions provides a high degree of current limitation.

  • Current-limitation protects downstream components against damaging thermal and magnetic effects of fault currents.

  • A superior, all-purpose, space-saving branch circuit fuse that meets most protection requirements up to 30 A.

  • Very compact physical size that’s only 13/32” x 1-1/2” (10 x 38 mm) with rejction tip.

  • Proper sizing can provide “No Damage” Type 2 coordinated protection for NEMA and IEC motor controllers.

  • Can be used where either a time-delay or a fast-acting fuse is needed, making selection easier and reducing spare fuse inventories for substantial cost reduction.

  • Superior protection for small horsepower motor circuits.

 

Recommended fuse blocks and holders:

Fuse amps

1-Pole

2-Pole

3-Pole

Modular open   blocks

UP TO 30

BCM603-1_

BCM603-2_

BCM603-3_

DIN-Rail   holders

UP TO 30

CHCC1D_

CHCC2D_

CHCC3D_


OPM-NG-_


OPM-1038_


OPM-1038_SW

Panel mount   holders

UP TO 30

HPS-RR


HPF-RR

In-line   holders

UP TO 30

HEY


HEZ


For additional information on Class CC fuse blocks and holders, see data sheets:

  • Modular open blocks no. 10241 (BCM)

  • DIN-Rail holders no. 3185 (CHCC), no. 1109 (OPM), no. 1102 (OPM-1038), no. 1103 (OPM-1038_SW)

  • Panel mount holders no. 2113 (HPS), no. 2114 (HPF)

  • In-line holders no. 2126 (HEY), no. 2130 (HEZ)