T600 600 volt Class T fuse blocks
Bussmann series T600 fuse blocks are open fuse blocks for use with Class T fuses up to 600 amps in various pole configurations from 1- to 3-poles. T600 blocks use Bussmann series JJS fuses.
Ratings
• Volts 600 V
• Amps up to 600 A
• SCCR 200 kA RMS Sym.
Agency information
• UL Listed, UL 4248, Guide IZLT, File E14853, CSA Certified, Class
6225-01, File 47235, CE
Flammability rating UL 94V0
Features
• Provide 1-, 2- and 3-pole housing for 600 Vac Class T fuses.
• High 200 kA RMS Sym. Short-Circuit Current Ratings
• Class T fuse blocks have a small foot print, providing substantial
space savings in equipment
Typical applications
• 600 V or less control systems
• 600 V or less individual control circuits
Catalog Numbers
Catalog no./terminals | Amps | Poles Fig. | Terminal AWG range/type | ||
Box lug | |||||
T60030-1SR | T60030-1CR | Up to 30 |
1 | SR 10-18 Cu CR 2-14 Cu/Al |
|
T60030-2SR | T60030-2CR | 2 | 1 | ||
T60030-3SR | T60030-3CR | 3 | |||
T60060-1SR | T60060-1CR | 31-60 | 1 | SR 10-18 Cu CR 2-14 Cu/Al |
|
T60060-2SR | T60060-2CR | 2 | 2 | ||
T60060-3SR | T60060-3CR | 3 | |||
_ | T60100-1C | 61-100 | 1 | 2/0-14 Cu/Al | |
_ | T60100-2C | 2 | 3 | ||
_ | T60100-3C | 3 | |||
_ | T60200-1C | 101-200 | 1 | 4 | 250kcmil-6 Cu/Al |
_ | 1B0089* | 3 | 5 | ||
_ | T60400-1C | 201-400 | 1 | 6 | 600kcmil-2/0 Cu/Al |
_ | T60600-1C | 401-600 | 1 | 7 | (2) 600kcmil-4/0 Cu/Al |
* UL Listed, Guide IZLT, File E14853, CSA Certified Class 6225-01, File 21455M18