170M - size 1* to 3, French style 690 Vac (IEC), 700 Vac (UL), 40 to 1500 A
Description
Square body French style high speed fuses for the protection of DC common bus, DC drives, power converters/rectifiers and reduced rated voltage starters. Available with Type T or K indicators for microswitches.
Specifications
Ratings
• Volts:
• 690 Vac (IEC)
• 700 Vac (UL)
• Amps: 40-1600 A
• Interrupting rating: 200 kA RMS Sym.
Operating class: aR
Agency information
• Designed and tested to IEC 60269 Part 4
• UL Recognized, E125085, JFHR2
• CSA Class 1422-30, (53787) on sizes (1, 2, 3) only
• CCC (please consult bulehighspeedtechnical@eaton.com for status)
• CE
Electrical Characteristics
Total Clearing I2t
The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).
Arc Voltage
This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%.
Power Losses
Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.
Catalog Numbers
Catalog Numbers (Amps) |
Electrical Characteristics |
|||
-E/ Type T Indicator For Micro |
-EKN/- Type K Indicator For Micro |
Size |
Amp |
voltage |
170M3308 |
170M3358 |
1 * |
40 |
690 Vac (IEC) 700 Vac (UL |
170M3309 |
170M3359 |
50 |
||
170M3310 |
170M3360 |
63 |
||
170M3311 |
170M3361 |
80 |
||
170M3312 |
170M3362 |
100 |
||
170M3313 |
170M3363 |
125 |
||
170M3314 |
170M3364 |
160 |
||
170M3315 |
170M3365 |
200 |
||
170M3316 |
170M3366 |
250 |
||
170M3317 |
170M3367 |
315 |
||
170M3318 |
170M3368 |
350 |
||
170M3319 |
170M3369 |
400 |
||
170M3320 |
170M3370 |
450 |
||
170M3321 |
170M3371 |
500 |
||
170M4308 |
170M4358 |
1 |
200 |
|
170M4309 |
170M4359 |
250 |
||
170M4310 |
170M4360 |
315 |
||
170M4311 |
170M4361 |
350 |
||
170M4312 |
170M4362 |
400 |
||
170M4313 |
170M4363 |
450 |
||
170M4314 |
170M4364 |
500 |
||
170M4315 |
170M4365 |
550 |
||
170M4316 |
170M4366 |
630 |
||
170M4317 |
170M4367 |
700 |
||
170M4318 |
170M4368 |
800 |
||
170M5308 |
170M5358 |
2 |
400 |
|
170M5309 |
170M5359 |
450 |
||
170M5310 |
170M5360 |
500 |
||
170M5311 |
170M5361 |
550 |
||
170M5312 |
170M5362 |
630 |
||
170M5313 |
170M5363 |
700 |
||
170M5314 |
170M5364 |
800 |
||
170M5315 |
170M5365 |
900 |
||
170M5316 |
170M5366 |
1000 |
||
170M6308 |
170M6358 |
3 |
500 |
|
170M6309 |
170M6359 |
550 |
||
170M6310 |
170M6360 |
630 |
||
170M6311 |
170M6361 |
700 |
||
170M6312 |
170M6362 |
800 |
||
170M6313 |
170M6363 |
900 |
||
170M6314 |
170M6364 |
1000 |
||
170M6315 |
170M6365 |
1100 |
||
170M6316 |
170M6366 |
1250 |
||
170M6317 |
170M6367 |
1400 |
||
170M6318 |
170M6368 |
1500 |
Features and Benefits
• Excellent DC performance
• Low arc voltage and low energy let-through (I2t)
• Low watts loss
• Superior cycling capability
Typical Applications
• DC common bus
• DC drives
• Power converters/rectifiers
• Reduced voltage starters
Series: European standard cubic French 690V 40-1500A
Current: 40-1500A
Voltage: 690Vac
Breaking capacity: 200 kA RMS Sym.
Certification:- CE
-Designed and tested to IEC 60269: Part 4
-UL Recognized