欧标方体平端 美式 1250V 50-1400A
170M — size 1* to 3, US style 1250 Vac (IEC), 1300 Vac (UL), 50 to 1400 A
Description
Square body US style bolted tags high speed fuses for the protection of DC common bus, DC drives, power converters/rectifiers and reduced rated voltage starters. Available with Type K indicator for microswitches.
Specifications
Ratings
• Volts:
• 1250 Vac (IEC)
• 1300 Vac (UL)
• Amps: 50-1400 A
• Interrupting rating: 100 kA RMS Sym.
Operating class: aR
Agency information
• CE
• Designed and tested to IEC 60269 Part 4
• UL Recognized*
• CSA*
• CCC*
* Consult your Bussmann series product representative for status.
Electrical Characteristics
Total Clearing I2t
The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).
Arc Voltage
This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%.
Power Losses
Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current
Catalog Numbers
Catalog Numbers (Amps) |
Electrical Characteristics |
|||
-FU/115 Without Indicator |
-FKE/115 Type K Indicator For Micro |
Size |
Amp |
voltage |
170M3688 |
170M3738 |
1* |
50 |
1250 Vac (IEC) 1300 Vac (UL) |
170M3689 |
170M3739 |
63 |
||
170M3690 |
170M3740 |
80 |
||
170M3691 |
170M3741 |
100 |
||
170M3692 |
170M3742 |
125 |
||
170M3693 |
170M3743 |
160 |
||
170M3694 |
170M3744 |
200 |
||
170M3695 |
170M3745 |
250 |
||
170M3696 |
170M3746 |
315 |
||
170M3697 |
170M3747 |
350 |
||
170M4688 |
170M4738 |
1 |
160 |
|
170M4689 |
170M4739 |
200 |
||
170M4690 |
170M4740 |
250 |
||
170M4691 |
170M4741 |
315 |
||
170M4692 |
170M4742 |
350 |
||
170M4693 |
170M4743 |
400 |
||
170M4694 |
170M4744 |
450 |
||
170M4695 |
170M4745 |
500 |
1100 Vac IEC |
|
170M4696 |
170M4746 |
550 |
||
170M4697 |
170M4747 |
630 |
1000 Vac IEC |
|
170M5688 |
170M5738 |
2 |
250 |
1250 Vac (IEC) 1300 Vac (UL) |
170M5689 |
170M5739 |
280 |
||
170M5690 |
170M5740 |
315 |
||
170M5691 |
170M5741 |
350 |
||
170M5692 |
170M5742 |
400 |
||
170M5693 |
170M5743 |
450 |
||
170M5694 |
170M5744 |
500 |
||
170M5695 |
170M5745 |
550 |
||
170M5696 |
170M5746 |
630 |
||
170M5697 |
170M5747 |
700 |
1100 Vac IEC |
|
170M5698 |
170M5748 |
800 |
||
170M5699 |
170M5749 |
900 |
1000 Vac IEC |
|
170M5700 |
170M5750 |
1000 |
||
170M6688 |
170M6738 |
3 |
315 |
1250 Vac (IEC) 1300 Vac (UL) |
170M6689 |
170M6739 |
350 |
||
170M6690 |
170M6740 |
400 |
||
170M6691 |
170M6741 |
450 |
||
170M6692 |
170M6742 |
500 |
||
170M6693 |
170M6743 |
550 |
||
170M6694 |
170M6744 |
630 |
||
170M6695 |
170M6745 |
700 |
||
170M6696 |
170M6746 |
800 |
1250 Vac (IEC) |
|
170M6697 |
170M6747 |
900 |
||
170M6698† |
170M6748† |
1000 |
1100 Vac (IEC) 1000 Vac (UL) |
|
170M6699† |
170M6749† |
1100 |
||
170M6700‡ |
170M6750‡ |
1250 |
1000 Vac (IEC/UL) |
|
170M6701‡ |
170M6751‡ |
1400 |
†Rated voltage (IEC) 1100.
‡Rated voltage (IEC) 1000V.
¥ UL Recognition at 1000V.
• Watts loss provided at rated current.
• Microswitch indicator ordered separately. See accessories on pages 185-186. • For fuse curves see pages 166 and 167.
Features and Benefits
• Excellent DC performance
• Low arc voltage and low energy let-through (I2t)
• Low watts loss
• Superior cycling capability
Typical Applications
• DC common bus
• DC drives
• Power converters/rectifiers